Elant LLP offers the high-voltage equipment of own production: KSO cameras of the KCO 285, KCO 293, KCO 299, KCO 366, KCO 399 series. You can order the KSO cameras, having filled and having sent us by e-mail the questionnaire on the basis of which the cost of production of the high-voltage equipment pays off.
Purpose of the KSO Cameras
Chambers with unilateral service are intended for completing of the distributing devices (DD) of alternating three-phase current with a frequency of 50 Hz, (6) kV of networks of 10 with isolated or a neutral. The KSO cameras can be used as distributing devices in systems of power supply, both a housing estate, and the industrial enterprises.
Design of the KSO cameras
The KSO cameras represent a welded design from bent steel holodnokatany sheets. Inside the equipment and tires of the main chains is placed. On front part metering devices and measurements are placed. For receiving idea of appearance of the KSO cameras and other high-voltage equipment we suggest to visit the section with photographic materials.
Service conditions of the KSO cameras:
- ambient temperature is from-25 With to + 35 C;
- height above sea level no more than 1000 m;
- relative humidity of air no more than 70;
- in the dry, closed heated and not heated rooms, environment is not explosive, not containing conducting dust, gases or vapors breaking operation of the device.
The KSO cameras are manufactured according to schemes of the main chains. Production of chambers according to non-standard schemes, developed by the manufacturer and coordinated with customers is also possible.
Execution of the KSO cameras
Technical characteristics of KSO
Name | Value |
---|---|
Rated voltage linear, kV | 10(6) |
The largest working tension, kV | 12(7,2) |
Rated current of combined tires, And | 630; 1000; 1500 |
Rated current of the main chains, And | 400; 630; 1000; 1500 |
Rated current of transformers of current, And | 50; 100; 150; 200; 300; 400; 600; 800; 1000; 1500 |
Rated current of combined tires and tire bridges, And | 630; 1000; 1500 |
Rated current of shutdown of the switch, kA | 20 |
Current of electrodynamic firmness, kA | 52 |
Current of thermal firmness, kA | 20 |
The rated voltage of secondary chains, in a chain of protection, management and alarm system of direct and alternating current, In | 220 |
In a chain of transformers of tension (protection, measurement, the account, AVR), In | 110 |