Products of other enterprises
Description
Chiller VMN065V Modular
Chiller with air and water cooling is a unit for cooling of water in fankoil or big system of the central conditioning. Central airs with chiller of air cooling are used on small real estate objects. Chillera with air and water cooling include a refrigerating contour, system of automatic equipment and fans, and also the hydraulic module. The water cooled with a chiller circulates in a hydraulic contour to which the heat exchanger is connected. A basic purpose of chiller with air and water cooling - to support comfortable temperature condition in rooms.Model | With the spiral compressor | ||||||||
VMA055V VMN055V | VMA060V VMN060V | VMA068M VMN068M | VMA088M VMN088M | VMA108M VMN108M | |||||
Power of cooling (R22) | kW | 55 | 60 | 68 | 88 | 108 | |||
Btu/h | 188,000 | 205,000 | 232,000 | 301,000 | 369,000 | ||||
TR | 16 | 17 | 19 | 25 | 31 | ||||
Power of heating (R22) | kW | 58 | 64 | 73 | 96 | 118 | |||
Btu/h | 198,000 | 219,000 | 249,000 | 328,000 | 403,000 | ||||
TR | 16.5 | 18.2 | 21 | 27.3 | 34 | ||||
Power of cooling (R407C) | kW | 52 | 57 | 65 | 84 | 103 | |||
Btu/h | 178,000 | 195,000 | 222,000 | 287,000 | 352,000 | ||||
TR | 15 | 16.2 | 18.5 | 24 | 29.2 | ||||
Power of heating (R407C) | kW | 55 | 61 | 69 | 91 | 112 | |||
Btu/h | 188,000 | 208,000 | 236,000 | 311,000 | 382,000 | ||||
TR | 16 | 17.3 | 20 | 26 | 32 | ||||
Having heated hot water (in addition) | Regeneration is warm | (R22) | kW | 16.5 | 18 | 20.4 | 26.4 | 32.4 | |
Btu/h | 57,000 | 62,000 | 70,000 | 90,000 | 111,000 | ||||
TR | 5 | 5.1 | 6 | 8 | 9.2 | ||||
(R407C) | kW | 15.7 | 17.1 | 19.4 | 25.1 | 30.8 | |||
Btu/h | 54,000 | 59,000 | 66,000 | 86,000 | 105,000 | ||||
TR | 4.5 | 5 | 6 | 7.1 | 9 | ||||
Water temperature on an entrance | ℃ | 50 | |||||||
Water temperature at the exit | ℃ | 55 | |||||||
Water exchange | m3/h | 2.9 | 3.1 | 3.5 | 4.6 | 5.6 | |||
Size of connecting tubes | 1 in | 1 in | 1 in | 1 in | 1 in | ||||
Compressor | Type | Spiral hermetic | |||||||
Input power | kW | 16.4 | 16.6 | 10.1×2 | 6.2×4 | 8.2×4 | |||
Power | 0-25-50-75-100% | 0-50-100% | 0-25-50-75-100% | ||||||
Fan | Type | Axial | |||||||
Input power | kW | 1.1 | 1.1 | 0.55×2 | 1.3×2 | 1.3×2 | |||
Air circulation | m3/h | 28,000 | 40,000 | 40,000 | |||||
Water heat exchanger | Type | Tubular | |||||||
Water exchange | m3/h | 9.5 | 10.5 | 12 | 16 | 19 | |||
Pressure | kPa | 40 | 40 | 42 | 45 | 43 | |||
Size of tubes | DN125 | ||||||||
Cooler | Type | R22/R407C | |||||||
Pressure | (kG) | 12.8/17.6 | 13.2/18 | 18 | 26 | 32 | |||
Broad tank | Capillary tubes | Broad gate | |||||||
Noise level | dB(A) | 67 | 68 | 71 | 73 | 73 | |||
Overall dimensions | Length | mm | 2030 | 2030 | 2165 | 2165 | 2165 | ||
Width | mm | 1060 | 1060 | 1290 | 1570 | 1570 | |||
Height | mm | 1730 | 1730 | 2020 | 2060 | 2060 | |||
Power | 3φ-380V-50HZ | ||||||||
Power consumption | kW | 17.5 | 17.7 | 21.3 | 27.4 | 35.4 | |||
The consumed current | A | 48. | 50 | 68 | 77 | 125 | |||
Weight | Kg | 720/740 | 740/760 | 830/880 | 1080/1160 | 1380/1460 |
Contact the seller
Chiller VMN060V Modular