Grounding conductor, switch three-phase JN15-12/31.5 (210)
- 19000 KZT/pcs - from 20 pcs
- Customer pickup,
- Courier
- In detail
Grounding conductor the switch of the internal JN15-12 installation for alternating current mains from the HAICI company (China).
The covered grounding conductor of the JN15-12 series is intended for safe grounding of the equipment when carrying out repair and maintenance, also it can be used in high-voltage distributing devices with a rated voltage of 10 kV or below and with a nominal frequency of 50 Hz. The grounding conductor conforms to requirements of the IEC60129 standard. It corresponds to GB1985 of alternating current of a high voltage.
Type and designation
JN15-12/31.5 (210) designation
Rated current k.z. 31.5 (kA)
The maintained short-term current of 40 (kA)
Spring drive
Rated voltage is 12 kV
project 15 No.
The closed type "N"
Grounding conductor of "J"
Distance between centers mm phases 210
Service conditions
ambient temperature: -15 °C ~ p-40 of °C;
installation height above sea level: no more than 1000 m;
relative humidity: average daily - no more than 95%, average monthly - no more than 90%;
pressure of saturated steam: average daily - no more than 2.2 kPa, average monthly - no more than 1.8 kPa;
installation: in fire-dangerous, explosive places;
condition: lack of pollution and strong vibration.
Available more than 50 pieces.