STK MARS heat meter (Du 15,20)
- Customer pickup,
- Courier
- In detail
- it is intended for measurement of thermal energy, volume and temperature of the heat carrier, and also for calculation of quantity of the impulses formed by metering devices with a pulse exit in apartments and cottages with a small expense of volume of the heat carrier;
- is established either in giving, or in the return pipeline in systems with horizontal distributing;
- at the expense of a counter complete set a pulse exit or RS485 integration into the automated system of data collection (ASKUE) is possible;
Equipment options
standard execution:
- brass case;
- optical interface;
execution with the RS485 interface:
- standard execution;
- the calculator is equipped with the RS485 interface;
execution with a pulse exit:
- standard execution;
- the calculator is equipped with a pulse exit (the impulse price adjusted);
all modifications is issued for installation both on the giving pipeline, and on the return pipeline;
all modifications are issued on three options of nominal expenses (see the table).
The heat meter of STK "MARS" measures, calculates, displays and transfers the following parameters:
- volume of the heat carrier, m ³;
- expense of the heat carrier, m ³ / h;
- heat carrier temperature in the giving and return pipelines, °C;
- difference of temperatures in the giving and return pipelines, °C;
- thermal power, Gcal/h;
- the saved-up thermal energy, Gcal;
- date and time;
- the water volume measured by the counters with a pulse exit connected to calculating entrances;
- serial number;
- codes of mistakes
Complete set
- compact heat meter;
- passport;
- set of connecting parts.
Name of parameter |
Norm for heat meters diameter of conditional pass, Du, mm |
|||||
Diameter of conditional pass, Du, mm |
15 |
20 |
||||
Maximum expense of Qmax, m3/hour |
1,2 |
2 |
3,0 |
3,0 |
5,0 |
|
Nominal expense, Qn, m3/hour |
0,6 |
1,0 |
1,5 |
1,5 |
2,5 |
|
Minimum expense, Qmin, m3/hour |
0,012 |
0,02 |
0,03 |
0,03 |
0,05 |
|
Relative error of measurement of volume, % |
± (2+0,05 · (Qn/Q)) |
|||||
Range of measurements of temperature, ºС |
from +0 to +130 |
|||||
Range of measurements of a difference of temperatures (Δt), ºС |
from +2 to +130 |
|||||
Absolute error of measurement of a difference of temperatures, °C |
± (0,2+0,005 · Δt) |
|||||
Maximum working pressure, MPa |
1,6 |
|||||
Loss of pressure at Qn, MPa, no more |
0,15 |
|||||
Protection class in accordance with GOST 14254 |
IP54 |
|||||
Tension of the built-in battery, In |
3,6 |
|||||
Battery service life, not less, years |
6 |
|||||
Service life, not less, years |
12 |
|||||
Assembly length is L, mm |
110 |
130 |