Trailer cable GUST-12/150-240/1200-L12 coupling
- Customer pickup,
- Courier
- In detail
- BrandRaychem
- Country of manufactureGermany
Application: for 3-wire cables with paper isolation and the general aluminum or lead cover of 6 and 10 kV.
Features of a design:
On veins oilproof tubes are established. The back is filled with oilproof mastic of yellow color and closed by the thermoseated carrying-out glove with glue, coming on a metal cover and veins. Tapes of yellow mastic for alignment of intensity of electric field are applied on the ends of fingers of a glove with calling on veins. On veins trekingostoyky tubes of red color are established. The end of isolation of a vein together with a tip or with the smoothed-out single-wire vein is pressurized by a cuff with glue. The fittings for nepayanny grounding are included in the package. A set with modification of L12 modification of L16 under M16 bolt includes cable bolted tips with an opening under a bolt of M12 and, respectively.
Note:
One set includes materials for 3 phases. The applied cable tips have to be tight. Length of veins can be determined by the place of installation. The minimum length of veins – 450 mm for Uo/U = 3,5/6 kV and 800 mm for Uo/U = 6/10 kV.